Castle Care-Tech Ltd. Engineering
Page 13 - 8 Chapter 13
Zone types:
The zone types available are:
Type Operation
00
Isolated
Factory default
Zone is programmed
out of operation
01 Fire
See
Note
Active at all times
Audible response: Full
(differentiated)
Communicator:
‘
Fire
’
signal
02 Gas Active at all times
Audible response: Full
(differentiated)
Communicator:
‘
Gas
’
signal
03 PA Active at all times
Audible response: Full
(differentiated)
Communicator:
‘
Hold
Up
’
and
‘
Zone PA
’
signals
04 Silent
PA
Active at all times
Audible response: None
Communicator:
‘
Hold
Up
’
and
‘
Zone PA
’
signals
When unset
:
Audible response:
Internal only
Communicator:
‘
Tamper
’
signal
05 Tamper
When set
:
Audible response: Full
Communicator:
‘
Tamper
’
+
‘
Intruder
’
signals.
06
Intruder
Active when set
Audible response: Full
Communicator:
‘
Intruder
’
signal
Type Operation
07 Final
Exit
(FX)
Active when set
–
initiates Entry time
If system not unset
before entry time
expires:
Audible response: Full
Communicator:
‘
Intruder
’
signal
08 Entry
Route
(ER)
Active when set, except
during entry time
Audible response: Full
Communicator:
‘
Intruder
’
signal
09 When Fully set, acts as
ER zone, as above
ER
/Area
FX
When
‘
Part
’
set, acts as
FX zone, as above
10 When Fully set, acts as
FX zone, as above
FX
/Area
ER
When
‘
Part
’
set, acts as
ER zone, as above
11 PTS Active during exit time
to complete setting
procedure.
No audible or
communicator
response.
Note: may be used to
act as a ‘doorbell’ by
use of ‘chime’
attribute.
12
Switcher
Active at all times.
No audible or
communicator
response.
Triggers associated
output for switching
other equipment.