Programming Manual EURO
RINS1291-3 Page: 51
The circuit resistance will be shown on any
on the inputs you choose (enter the input
number).
OC: Open Circuit, CC: Closed Circuit
DF: Detector Fault, DM: Detector Masked
DT: Detector Tamper
Press the key and you may view the
same for each ZEM, Keypad or Reader. You
will then be sent back to ‘View Inputs’.
Press the key to do a Slow Scan if using
iD biscuits. Or Press the key for
Calibration
Slow Scan For iD
On the Slow Scan the system ceases normal
iD scanning to permit the ‘reset’ voltage on
the iD line to be measured with a standard
meter.
If you would like to calibrate the iD reset and
PSU voltage of the EURO system, Press the
key and enter .
The iD Reset voltage may be adjusted using
the and keys. (This can be checked
on the terminals E3 and E4).
To calibrate, disconnect all iD wiring from
endstation terminals, and place a calibrated
digital volt meter across E3 and E4. The
voltage should be 3.5V.
Press the key
Repeat the process for the PSU voltage if
desired. This can be checked on the auxiliary
and battery terminals.
To calibrate, place a calibrated digital volt
meter across the auxiliary’s and battery
terminals. The voltage should be 13.7V.
Press the key twice, you will be returned
to the engineer menu.