Programming Manual EURO
RINS1291-3 Page: 13
4.4.4 Input Response Time
This selects the time that an input trigger must be present before the whole system responds
by generating an alarm, and is programmable from 100mS (0.1 seconds) to 3000mS (3
seconds). Note:
Settings above 400mS do not comply with PD6662/EN50131. If used in a
BS4737 installation, setting should be between 300 and 800mS. 400mS is selected as
default.
4.4.5 Input XDF
DO NOT CHANGE THIS SETTING UNLESS INSTRUCTED TO BY CUSTOMER SUPPORT.
Choose Mode
Using the and keys, scroll to
‘CHOOSE MODE?’. Press the key
Detection Mode
Enter : iD. Enter : EOL
Press the key
The End of Line Range
Enter : 1k. Enter : 2k2
Enter : 4k7. Press the key
The End of Line Mode
Enter : for SR Enter : for DR
Press the key
The Input Response
Select the required input response – using
the and keys to scroll through the
different responses: 100ms to 3000ms.
This should be left at default (400ms). Press
. Input XDF
will be displayed, do not
alter this and press the key
4.5 Install ZEM
Any Zone Expander Modules (ZEMs) installed on the EURO system must be enabled by the
‘Install ZEM’ function.
Install ZEM
Using the and keys, scroll to
‘INSTALL ZEM?’. Press the key