Programming Manual EURO
RINS1291-3 Page: 47
4.20 Engineer Tests
The Test function allows the engineer to test inputs, outputs, batteries and the siren.
4.20.1 Sounds To Play*
This function allows you to listen to the different tones the EURO system makes. They have a
choice of: Chime, Chime Follow, Exit, Exit Fault, Entry, Tech Fault, Tamper, Alarm, PA, and
Fire. *This feature is not available on the EURO 28
4.20.2 Walk Test
Please note that the walk test feature can only be used when engineer mode is exited after the
programming of inputs.
This function allows the engineer to test all programmed inputs on the system. The inputs that
haven’t been activated will be shown on the display. Once all the inputs have been walk
tested, ‘Walk Test Completed’ will be displayed.
When walk-testing a double-knock detector, it must be triggered twice within the preset
period. When testing dual-trip detectors you must first open detector one and then trigger the
second detector; next open the second detector and trigger the first detector.
4.20.3 Soak Control
Any input may be placed on ‘soak test’ to prevent it from generating an alarm. If the input
triggers whilst the system is set, it will indicate the activation and enter the details in the
system log. You can also enter the number of days you would like the soak test to last, after
this period the inputs will be active.
4.20.4 Test Siren
Any outputs programmed with a siren or strobe configuration will be activated.
4.20.5 Do Battery Load Test
Battery Test
The system performs a check of the battery operation every 10 seconds, by dipping the power
supply voltage momentarily, and measuring the system voltage. If the battery voltage
measured is below 12.0V, or the battery fuse has failed, a ‘BATTERY FAULT 100’ warning will
be generated.
Battery Load Test
EURO Systems may be programmed to perform an automatic battery load test at every power
supply at 7.00am each day. This will drop the power supply voltage below the battery voltage,
whilst monitoring the system diagnostics. The test will NOT take place if:
The End Station siren and strobe Output are live
The system is in Engineer Mode
Any battery faults exists
Any mains fault exists
The site option is not selected
If the test has already started, it will be aborted if any of these conditions apply, other than
entry into Engineer Mode. If the test is aborted, it will NOT be performed until the next day.
This is selected in SITE OPTIONS under “Do Battery Load Test”. The test may also be
performed as required, under engineer control.
4.20.6 Test Outputs
The engineer can test all the Programmable Outputs on the End Station and the output
module. This test can also be used to test the STU/ATE pins, all you need to do is select the
output types you have chosen for the pins and test them, the signal will be then sent out on
both the programmable outputs and the STU/ATE pins.