EURO Programming Manual
Page: 12 RINS1291-3
4.2 Inhibit Fire/HU
This function allows you to select if you would like the EURO system to respond to or inhibit
Fire and Hold Up Alarms during the Engineers Menu.
Using the and keys, scroll to
INHIBIT FIRE/HU?
Press the key
The following will be displayed:
Enter : for
Enter : for (Default)
Press the key
You will be returned to the Engineer Menu.
4.3 Software Revision
This option identifies the software version number, software serial number and product.
Using the and keys, scroll to
SOFTWARE REVISION?
Press the key.
The version number will be displayed.
In this example, the panel is a Euro 1, 76
version 6.04a.
Press the key.
You will be returned to the Engineer Menu.
4.4 Choose Mode
4.4.1 Detection Mode
The panel can be either operated as an End of Line panel or an iD panel. For more information
about the input mappings please see page 6. EOL is selected as default.
4.4.2 The End of Line Range*
This programs the panel to operate with different resistor values:
1K = Alarm: 1K, Tamper: 1K.
2K2 = Alarm: 4K7, Tamper: 2K2. (Default)
4K7 = Alarm: 4K7, Tamper: 4K7.
*This feature is not available on the Euro 28
4.4.3 SR or DR
This programs whether the whole alarm panel and any ZEMs will be used in Singe End of Line
mode (SR) or Double End of Line (DR) resistor mode. (DR is selected as default)